400G SR4 vs DR4 vs FR4 optical link solutions

400G SR4 vs DR4 vs FR4: How to Choose the Right 400G Optical Transceiver for Your Link

Short answer

  • 400G SR4: up to 100m on OM4 (60m on OM3) multimode fiber, MPO-12 connector. Best for in-rack and same-row links.
  • 400G DR4: up to 500m on OS2 single-mode parallel fiber, MPO-12/APC connector. This is the one to pick if you need to break 400G out to 4 × 100G.
  • 400G FR4: up to 2km on a single OS2 single-mode fiber pair, LC duplex connector. A point-to-point 400G link with no breakout.
Link distance Fiber Connector Pick
Up to 100m (OM4) / 60m (OM3) Multimode OM3/OM4 MPO-12 (our SKU: MPO-12/APC) 400G QSFP-DD SR4
Up to 500m, or any length that needs 4 × 100G breakout Single-mode OS2, parallel (8 fibers) MPO-12/APC 400G QSFP-DD DR4
Up to 2km Single-mode OS2, duplex (2 fibers) LC duplex 400G QSFP-DD FR4

If your multimode link must match an SR4+ specification, see What about SR4+? below. Then check the far-end optic and your switch's port type before you order.

Why the choice matters

400G remains the workhorse speed in many data center networks. It is the default uplink in a large share of leaf-spine fabrics, the bridge between legacy 100G racks and newer 800G spines, and a common choice for budget-conscious refreshes. But once you have decided on 400G, a second question follows immediately: which 400G optic do you actually order?

The three most common short- and mid-reach options, 400G SR4, 400G DR4, and 400G FR4, all deliver 400 Gbps, often in the same QSFP-DD form factor. What separates them is the physical link: wavelength, fiber type, connector, reach, and whether the port can be broken out to 100G. Choosing the wrong one usually doesn't show up until installation day, when the fiber plant, patch panels, or far-end device don't match.

This guide compares SR4, DR4, and FR4 side by side and gives you a practical checklist to match each optic to your link.

1. Quick Comparison: 400G SR4 vs DR4 vs FR4

Parameter 400G SR4 400G DR4 400G FR4
IEEE reference 400GBASE-SR4 (802.3db) 400GBASE-DR4 (802.3bs) 400GBASE-FR4 (802.3cu)
Wavelength 850nm 1310nm 4 CWDM wavelengths around 1310nm
Fiber type Multimode (OM3/OM4) Single-mode (OS2) Single-mode (OS2)
Typical reach 100m OM4 / 60m OM3 500m 2km
Optical lanes 4 × 100G PAM4, parallel fiber 4 × 100G PAM4, parallel fiber 4 × 100G PAM4, multiplexed onto one fiber pair
Connector MPO-12 MPO-12/APC LC duplex
Fibers used 8 (4 Tx + 4 Rx) 8 (4 Tx + 4 Rx) 2 (1 Tx + 1 Rx)
4 × 100G breakout Yes (to 100G SR1-type optics, host permitting) Yes (to 100G DR-type optics) No (one 400G link per fiber pair)
Typical placement In-rack, same row, ToR to leaf Leaf to spine, row to row, breakout to 100G Across data halls, between buildings on a campus

All three use PAM4 modulation and 100G-per-lane optics, so the choice comes down to distance, existing fiber, and topology rather than raw performance.

2. 400G SR4: Short Reach over Multimode Fiber

How it works

400G SR4 uses four 850nm VCSEL lasers, each carrying 100G PAM4 over its own multimode fiber, with four more fibers for the receive direction. The link terminates on a single MPO-12 connector.

When SR4 is the right choice

  • Short links inside the rack or row. Top-of-rack to leaf, server-adjacent switching, and GPU-to-switch links in AI clusters where the distance stays well within 100m on OM4.
  • Existing multimode plant. If your data hall already runs OM3/OM4 MPO trunks, SR4 lets you reuse them. Keep in mind that reach drops on OM3 (60m versus 100m on OM4).
  • Lowest cost per port. VCSEL-based multimode optics are typically the most economical 400G option for short links.

Watch-outs

  • Do not mix multimode SR4 with single-mode infrastructure. The fiber type has to match end to end.
  • MPO polarity and end-face polish (APC vs UPC) must match across the trunk, cassettes, and patch cords.
  • Plan for growth. If tomorrow's link could exceed 100m, single-mode (DR4/FR4) may be the safer long-term investment.

YYGL product: Yiyuan 400G QSFP-DD SR4 850nm 100m MPO-12 Multimode Optical Transceiver: 100m on OM4 / 60m on OM3, MPO-12/APC, DOM supported.

What about SR4+?

Some vendors also offer an enhanced short-reach multimode variant, often labelled SR4+, that is designed to go further than standard SR4 over multimode fiber. Reach and interoperability for these variants depend on the specific product and the host platform, so always confirm the rated reach, the fiber grade, and the far-end optic before mixing an SR4+ with a standard SR4.

YYGL Optical also lists a 400G QSFP-DD SR4+ multimode optical transceiver: 850nm, 4 × 100G PAM4, OM3/OM4 multimode fiber, MPO interface, DOM supported. Its listing describes extended reach over OM4 compared with standard SR4 but does not state a longer distance figure, so contact our team to confirm whether it fits your link.

3. 400G DR4: 500m over Parallel Single-Mode Fiber

How it works

400G DR4 also uses four parallel 100G PAM4 lanes, but at 1310nm over single-mode fiber. Like SR4, it uses an MPO-12 connector with eight active fibers. Single-mode transmission is what extends the reach to 500m.

When DR4 is the right choice

  • Leaf-to-spine and row-to-row links that are too long for multimode but don't need 2km.
  • 400G-to-100G breakout. Because each of the four lanes is an independent 100G single-mode channel, a single 400G DR4 port can feed four 100G single-lambda (100G DR-type) optics through an MPO-to-4×LC breakout cable. This is one of the most common ways to connect a new 400G switch to existing 100G equipment.
  • Single-mode structured cabling built on MPO trunks.

Watch-outs

  • DR4 uses APC (angled) MPO connectors. Mating APC with UPC damages end faces and degrades the link, so verify every patch cord and cassette.
  • Breakout only works if the host switch supports splitting the port into 4 × 100G and the far-end optics are the matching 100G single-lambda type. Check the switch configuration guide.
  • Parallel fiber means eight fibers per link. In large fabrics this drives up trunk fiber count compared with duplex options.

YYGL product: Yiyuan 400G QSFP-DD DR4 1310nm 500m MPO-12 Single-Mode Optical Transceiver: 500m over OS2, MPO-12/APC, 400GBASE-DR4, DOM supported.

4. 400G FR4: 2km over a Single Fiber Pair

How it works

400G FR4 multiplexes four 100G PAM4 wavelengths on the CWDM grid around 1310nm onto a single single-mode fiber in each direction. The result is a full 400G link over just two fibers with a standard LC duplex connector, at up to 2km.

When FR4 is the right choice

  • Longer intra-campus links: between data halls, floors, or buildings up to 2km.
  • Reusing duplex LC single-mode cabling. If your patch panels and trunks are already LC duplex OS2, FR4 can usually reuse them without re-cabling to MPO.
  • Fiber-constrained routes. Where conduit space or available fiber pairs are limited, FR4 needs only two fibers per 400G link, compared with eight for SR4/DR4.

Watch-outs

  • FR4 is a point-to-point 400G optic. Because the four lanes share one fiber, it does not break out to 4 × 100G. If you need breakout, use DR4.
  • Both ends must be FR4 (same CWDM wavelength plan). An FR4 does not interoperate with a DR4 or an LR-class optic.
  • Budget for the higher loss of longer runs and multiple patch points, and keep LC connectors clean. Contamination is one of the most common causes of link errors.

YYGL product: Yiyuan 400G QSFP-DD FR4 1310nm 2km LC Duplex Single-Mode Optical Transceiver: 2km over OS2, CWDM4, LC duplex, DOM supported.

DR4 vs FR4 at a glance

If your link is already on single-mode fiber, the choice is between DR4 and FR4. Start with three questions. First, what fiber is installed? DR4 needs parallel MPO-12/APC trunks with eight active fibers, while FR4 runs over a standard LC duplex pair. Second, how far is the link? DR4 is listed at 500m and FR4 at 2km over OS2. Third, do you need breakout? DR4 can split into four 100G single-lambda links when the host supports it, while FR4 is a point-to-point 400G link with no breakout. Whichever you choose, the far end must use the same optic type, or a supported 100G breakout partner for DR4. Both are available as 400G QSFP-DD modules.

5. Compatibility Caveats That Apply to All Three

Matching reach and fiber is only half of the job. A 400G link also needs both ends, and the host switch, to agree on the following:

Same standard at both ends

The two ends of a link must use the same optical interface: SR4 to SR4, DR4 to DR4 (or DR4 to 4 × 100G DR-type in breakout), FR4 to FR4. Same data rate alone is not enough.

Form factor and port type

All three optics are available in QSFP-DD, the most common 400G port on Ethernet switches (see our 400G QSFP-DD transceivers). Some platforms use OSFP ports at 400G instead (see our 400G OSFP transceivers). Confirm the cage type on your switch before ordering, and avoid relying on adapters for production links unless the switch vendor supports them.

FEC and host settings

400G Ethernet over 100G PAM4 lanes depends on Reed-Solomon forward error correction (RS-FEC). FEC mode, port speed, and breakout settings must be configured consistently on both hosts. Most link-up issues on new 400G deployments come down to mismatched port configuration, not faulty optics.

Vendor coding (EEPROM)

Switches from Cisco, Arista, NVIDIA Mellanox, Juniper, and Dell read the transceiver's EEPROM and may check vendor coding. Compatibility depends on the host platform. Please share your switch model, software version, module type, link distance and fiber type so we can check coding and compatibility before you order. DOM (digital optical monitoring) should also report temperature, voltage, bias current, and Tx/Rx power to your NMS.

Cabling hygiene

Match fiber type (OM3/OM4 vs OS2), connector (MPO-12 vs LC), polish (APC vs UPC), and MPO polarity across the whole channel. Inspect and clean every end face before insertion.

6. Buyer's Checklist: Picking SR4, DR4, or FR4

Before you request a quote, answer these questions:

  1. What is the longest link length, including patch cords and cross-connects? Up to 100m on OM4 points to SR4, up to 500m to DR4, and up to 2km to FR4.
  2. What fiber is already installed? Multimode MPO points to SR4, single-mode MPO to DR4, and single-mode LC duplex to FR4.
  3. Do you need to break out 400G to 4 × 100G? If so, choose DR4 (or SR4 where the host supports multimode breakout). FR4 does not break out.
  4. How many fibers are available on the route? If fiber is scarce, FR4 uses two fibers versus eight.
  5. What is at the far end? It needs the same optic type, or a supported 100G breakout partner.
  6. Which switch platform and port type? Note the brand (Cisco, Arista, NVIDIA Mellanox, Juniper, or Dell), model, OS version, and whether the port is QSFP-DD or OSFP.
  7. Do you need DOM in your monitoring stack? Confirm that DOM fields are readable on your platform.
  8. Are you planning an 800G upgrade? Consider how today's fiber choice (multimode vs single-mode, MPO vs LC) will carry over to 800G SR8, DR8, or 2×FR4 optics later.

Conclusion

SR4, DR4, and FR4 all deliver 400 Gbps. The right choice depends on the link they have to serve:

  • SR4 for the shortest, most cost-sensitive multimode links inside the rack or row.
  • DR4 for 500m single-mode links and 400G-to-100G breakout.
  • FR4 for up to 2km over a single LC duplex fiber pair.

Confirm the reach, fiber, connector, far-end optic, and switch coding before you order, and you avoid the most common installation-day surprises. If you are also planning the move to 800G, see our 800G vs 400G optical transceivers upgrade guide.

YYGL Optical (毅远光联), also known as Yiyuan Guanglian or Yiyuan Optical Link, supplies compatible 400G QSFP-DD SR4, SR4+, DR4, and FR4 transceivers, along with 800G and 1.6T optics, for Cisco, Arista, NVIDIA Mellanox, Juniper, and Dell platforms. Each module is tested before shipment. Request a Quote with your switch model and link distance, and our team will help you choose the right optic.

Contact Us

Request a quote: yiyuanguanglink.com/pages/request-a-quote-yygl
Email: yygl@yiyuanguanglian.cn
WhatsApp: +86 15072333382
LinkedIn: YYGL Optical company page

Direct Manufacturer Engineering Support

Looking for High-Speed Optics for Your AI Clusters or Data Center Upgrades?

YYGL Optical engineers and manufactures high-performance 10G to 1.6T transceivers (OSFP, QSFP-DD, SFP+) pre-coded and 100% tested for Arista, Cisco, NVIDIA Mellanox, and Juniper switches. Evaluation samples and direct factory wholesale pricing are available for network engineering teams.

✓ 100% Host Switch Pre-Coded ✓ Bit Error Rate (BER) < 1E-12 Verified ✓ Direct Factory Wholesale & RFQ
返回博客