Reach matrix of 400G SR4 and VR4 on OM3, OM4 and OM5 fiber from 10 m to 100 m, showing where both types fit, where only SR4 fits, and the IEEE 802.3db channel loss limits.

400G SR4 vs VR4: How Far Can Each Go on OM3, OM4 and OM5 Multimode Fiber?

Choose 400G VR4 only when every multimode link is 30 m or shorter on OM3, or 50 m or shorter on OM4 or OM5, and the channel loss stays within 1.6 dB (OM3) or 1.7 dB (OM4/OM5). Choose 400G SR4 when any link runs past those limits, up to 60 m on OM3 or 100 m on OM4/OM5, within 1.7 dB or 1.8 dB of channel loss. OM5 adds no reach over OM4 for either type, because both run on a single 850 nm wavelength.

Both are IEEE 802.3db physical layers (IEEE Std 802.3, Clause 167): four lanes of 100G PAM4 at 850 nm over eight multimode fibers with an MPO connector. The difference is the reach and loss they are specified for, not the form factor. This guide sets out the standard figures, a loss check you can repeat for your own patch path, and how the QSFP112, QSFP-DD and OSFP-RHS versions in our catalog differ. Standard figures come from IEEE 802.3db as summarized by the TIA Fiber Optics Tech Consortium (FOTC); module figures come from our own product pages.

What is the difference between 400GBASE-SR4 and 400GBASE-VR4?

VR4 ("very short reach") and SR4 ("short reach") were defined together in IEEE 802.3db (2022). Both use 106.25 GBd PAM4 per lane, four transmit and four receive fibers, and an MPO connector. VR4 targets server-to-switch links inside a rack or row. SR4 targets longer switch-to-switch links across a row or small hall. In the 802.3db discussions the two variants were described as the VR type for 30 m on OM3 and 50 m on OM4, and the SR type for 60 m on OM3 and 100 m on OM4.

Parameter (IEEE 802.3db, per TIA FOTC) 400GBASE-VR4 400GBASE-SR4
Wavelength 850 nm 850 nm
Lanes / fibers 4 × 100G PAM4 / 8 fibers 4 × 100G PAM4 / 8 fibers
Operating range, OM3 0.5 to 30 m 0.5 to 60 m
Operating range, OM4 and OM5 0.5 to 50 m 0.5 to 100 m
Max channel insertion loss, OM3 1.6 dB 1.7 dB
Max channel insertion loss, OM4/OM5 1.7 dB 1.8 dB
Max cabling skew 79 ns 79 ns
Min modal bandwidth at 850 nm OM3 2,000 MHz·km; OM4 4,700 MHz·km OM3 2,000 MHz·km; OM4 4,700 MHz·km
Breakout counterpart (one lane) 100GBASE-VR1, up to 50 m 100GBASE-SR1, up to 100 m

One rule follows from the table. Treat SR4 and VR4 as different optical specifications and put the same specification at both ends of a link. Do not pair an SR4 module with a VR4 module and expect SR4 reach.

How far can 400G SR4 and VR4 go on OM3, OM4 and OM5?

Use this table to choose by link length and fiber grade. Find the row for your longest link in the batch, not the average.

Longest link in the batch OM3 OM4 OM5
Up to 30 m VR4 or SR4 VR4 or SR4 VR4 or SR4
31 to 50 m SR4 only VR4 or SR4 VR4 or SR4
51 to 60 m SR4 only SR4 only SR4 only
61 to 100 m Beyond both; re-cable to OM4/OM5 or use single-mode SR4 only SR4 only
Over 100 m Beyond both multimode types: plan single-mode DR4 (500 m) or FR4 (2 km)

Every cell still needs the loss check in the next section. A short link with too many dirty or high-loss connections can fail where a longer, cleaner link passes.

Does OM5 give 400G SR4 more reach than OM4?

No. OM5 has the same effective modal bandwidth as OM4 at 850 nm. Its extra value is that it is also characterized up to 953 nm, which only helps multi-wavelength (shortwave WDM) optics. SR4 and VR4 use one wavelength, 850 nm, so IEEE lists OM4 and OM5 together with the same range and loss limits. If you are buying new fiber only for SR4 or VR4, OM4 meets the specification. If you already have OM5 installed, it works the same way as OM4 for these modules.

Can I reuse existing OM3 for 400G multimode?

Yes, within the shorter OM3 limits: 30 m for VR4 and 60 m for SR4. The OM3 loss allowance is also 0.1 dB tighter than OM4 for each type. Check the fiber count as well. SR4 and VR4 use 8 of the 12 positions in an MPO-12 connector, so an MPO-12 trunk works. A plant built from LC duplex pairs needs an MPO-to-LC cassette or a re-termination, and each one adds a mated connection to the loss count.

How do I check whether my patch path fits the loss budget?

Over these short distances the fiber uses only a small part of the budget, so the connections decide whether a link passes. ANSI/TIA-568.3 allows cabled multimode fiber up to 3.5 dB/km at 850 nm and a mated connector pair up to 0.75 dB. Your cabling vendor's rating for low-loss MPO assemblies is often lower. Use the vendor's rated value where you have one.

  1. Add up the fiber length from module to module, including patch cords: length in km × 3.5 dB/km.
  2. Count every mated MPO or LC connection in the path (patch panels, cassettes, trunk breakouts) and multiply by the rated loss per connection.
  3. Compare the total with the IEEE channel limit for that module type and fiber grade.
  4. If you already have measured loss from an installed-link certification test, use it instead of the estimate.
Illustrative example (assumed values) Fiber loss Connection loss Total VR4 limit, OM4 (1.7 dB) SR4 limit, OM4 (1.8 dB)
45 m OM4, 2 mated MPO connections at 0.35 dB each 0.16 dB 0.70 dB 0.86 dB Within Within
45 m OM4, 4 mated MPO connections at 0.35 dB each 0.16 dB 1.40 dB 1.56 dB Within, 0.14 dB left Within, 0.24 dB left
45 m OM4, 3 mated MPO connections at the 0.75 dB TIA maximum 0.16 dB 2.25 dB 2.41 dB Over Over
90 m OM4, 2 mated MPO connections at 0.35 dB each 0.32 dB 0.70 dB 1.02 dB Beyond 50 m range Within

The per-connection values in this table are planning assumptions, not measurements of a specific product. The example shows two points. Moving from VR4 to SR4 buys only 0.1 dB of loss allowance, so SR4 does not rescue a path with too many connections. And connector grade and cleanliness matter more than the last few meters of fiber. Inspect and clean every MPO end-face before turn-up. A contaminated MPO end-face can add enough loss to fail a link that passes on paper.

Which 400G SR4 and VR4 form factor do I need: QSFP112, QSFP-DD or OSFP-RHS?

Within each optical type, the fiber side is the same across form factors. The form factor and host electrical interface must match the port. Figures are from our product pages.

Module Optical type Reach (OM3 / OM4) Host electrical interface Max power Connector
400G QSFP112 VR4 850nm 50m VR4 30 m / 50 m 4 × 100G PAM4 ≤9.0 W MPO-12/APC
400G QSFP-DD VR4 850nm 50m VR4 30 m / 50 m 8 × 50G PAM4 ≤8.0 W MPO-12/APC
400G OSFP-RHS VR4 850nm 50m VR4 30 m / 50 m 4 × 100G PAM4 ≤9 W MPO-12/APC
400G QSFP112 SR4 850nm 100m SR4 60 m / 100 m 4 × 100G PAM4 ≤9 W MPO-12/APC
400G QSFP-DD SR4 850nm 100m SR4 60 m / 100 m Per product page and host port ≤8 W MPO-12/APC
400G OSFP-RHS SR4 850nm 100m SR4 70 m / 100 m (product page) 4 × 100G PAM4 ≤9.0 W MPO-12/APC

Two notes on this table. First, the QSFP-DD VR4 takes 8 × 50G lanes on the host side and sends 4 × 100G lanes on the fiber, so it suits QSFP-DD ports with 50G host lanes. QSFP112 and OSFP-RHS modules expect 100G host lanes. Our 400G QSFP112 vs QSFP-DD vs OSFP-RHS form-factor guide explains how to read the port type, and 100G-lane vs 200G-lane optics covers the lane-rate question. Second, the OSFP-RHS SR4 product page lists 70 m on OM3, which is longer than the 60 m IEEE operating range for 400GBASE-SR4. For a mixed-vendor or mixed-module link, plan to the lower IEEE figure unless both ends are confirmed for the longer one.

Compatibility depends on the host platform. Please share your switch model, software version, module type, link distance and fiber type so we can check coding and compatibility before you order. We can check coding options for Cisco, Arista, NVIDIA Mellanox, Juniper and Dell host platforms. YYGL Optical is an independent optics supplier; we are not those brands and we do not claim affiliation with them.

When should I skip multimode and plan 400G DR4 or FR4?

Multimode stops at 100 m for 400G SR4. If your longest link is near that limit, if the path will gain more patch panels later, or if the same trunk may carry 800G, compare single-mode before you buy. Our 400G SR4 vs DR4 vs FR4 guide covers the move to 500 m DR4 and 2 km FR4. For the 800G version of the same short-reach question, see 800G SR8 vs VR8 vs DR8. For reusing trunks during an upgrade, see migrating from 400G to 800G and 1.6T: cabling reuse and breakout.

Pre-order checklist for 400G SR4 or VR4

  • Longest link: measured module-to-module length, patch cords included, for every link in the batch.
  • Fiber grade: OM3, OM4 or OM5, confirmed from cable jacket print or as-built records.
  • Connections: number of mated MPO/LC connections per path and their rated loss, or certification test results.
  • Optical type: VR4 (≤30 m OM3, ≤50 m OM4/OM5) or SR4 (≤60 m OM3, ≤100 m OM4/OM5), with the same type at both ends.
  • Connector and polarity: MPO-12 APC on the modules; trunk and patch cord end-face type and polarity method matched to the modules.
  • Host port: QSFP112, QSFP-DD or OSFP-RHS, and 50G or 100G host lanes.
  • Breakout: whether the host supports 4 × 100G breakout to 100GBASE-VR1/SR1 at the far end.
  • Coding: switch or NIC model and software version for each end.
  • Power and thermal: port power class against the module's maximum power.

Send the list to us through the request a quote page and we will reply with matching part numbers.

FAQ

Can a 400G VR4 module run 100 m on OM4?

No. IEEE 802.3db specifies 400GBASE-VR4 to 50 m on OM4 and OM5 and 30 m on OM3. Use SR4 for links up to 100 m on OM4/OM5.

Can I connect a 400G SR4 module to a 400G VR4 module?

Plan on the same optical type at both ends. SR4 and VR4 are separate IEEE specifications, and a mixed pair is not specified to deliver SR4 reach.

Is OM5 worth it for 400G SR4 or VR4?

Not for reach. IEEE gives OM5 the same range and loss limits as OM4 for both types. OM5 only adds reach for multi-wavelength multimode optics.

Do 400G SR4 and VR4 need MPO-12 or MPO-16?

They use 8 fibers, carried on an MPO-12 connector; our SR4 and VR4 modules use MPO-12/APC. MPO-16 is for 16-fiber types such as 400G SR8.

Can I break out 400G SR4 into four 100G links?

The optics are four 100G lanes, matching 100GBASE-SR1 (up to 100 m); VR4 matches 100GBASE-VR1 (up to 50 m). Whether a port can run in 4 × 100G breakout depends on the host, so confirm the switch model and software first.