Decision chart for 400G DR4 versus DR4+: a distance bar showing DR4 up to 500 m and DR4+ up to 2 km on OS2 fiber, and a flow chart that picks DR4+ when the link exceeds 500 m or worst-lane loss exceeds 3.0 dB.

400G DR4 vs DR4+: When Does a 500 m Single-Mode Link Need the 2 km Optic?

Choose a 400G DR4 module when your longest single-mode link is 500 m or shorter and its measured channel loss at 1310 nm is 3.0 dB or less. Choose a 2 km-class DR4+ module when the link is longer than 500 m, or when the patch path loses more than 3.0 dB even though the run is short. The IEEE 2 km parallel specification, 400GBASE-DR4-2, allows up to 4.0 dB. Both types use the same eight single-mode fibers and MPO-12 connector, so you can change the optic without re-cabling.

This guide covers the standard limits behind that rule and a loss check you can repeat for your own patch path. It also shows which form factors in our catalog offer each type. Standard figures come from IEEE 802.3, as summarized in the TIA Fiber Optics Tech Consortium (FOTC) application overviews for 400GBASE-DR4 and 400GBASE-DR4-2. Module figures come from our own product pages.

What is the difference between 400G DR4 and DR4+?

400GBASE-DR4 is defined in Clause 124 of IEEE Std 802.3, first published in IEEE 802.3bs (2017). It sends four lanes of 100G PAM4 at 1310 nm over four transmit and four receive single-mode fibers, for at least 500 m. "DR4+" is an industry name, not an IEEE name. It describes the same parallel 1310 nm design built for 2 km. IEEE standardized that reach as 400GBASE-DR4-2 in IEEE 802.3df (2024). The 802.3df baseline proposal said the 2 km PHY was intended to build on 400GBASE-DR4 and the single-lane 100GBASE-FR1 specification.

The two names do not always mean the same thing. A module sold as "DR4+" may follow 400GBASE-DR4-2, or it may be a vendor-specific extended-reach DR4. Always check the datasheet for the reach, the channel loss it supports and the standard it references.

Parameter (per TIA FOTC summaries of IEEE 802.3) 400GBASE-DR4 400GBASE-DR4-2 (2 km "DR4+" class)
Standard IEEE 802.3bs (2017), Clause 124 IEEE 802.3df (2024)
Wavelength 1310 nm 1310 nm
Lanes / fibers 4 × 100G PAM4 / 8 single-mode fibers 4 × 100G PAM4 / 8 single-mode fibers
Connector MPO MPO
Max channel insertion loss 3.0 dB 4.0 dB
Connection and splice allocation used to calculate reach 2.75 dB 3.0 dB
Operating range, OS2 / indoor-outdoor cable 2 m to 500 m 2 m to 2 km
Operating range, OS1a (informative only) 2 m to 250 m 2 m to 1 km
Max cabled fiber attenuation assumed (OS2) 0.4 dB/km 0.4 dB/km

Most of the loss allowance goes to connections, not fiber. On a 500 m DR4 link, OS2 cabled fiber uses only about 0.2 dB of the 3.0 dB budget. On a 2 km DR4-2 link it uses about 0.8 dB of the 4.0 dB budget. Connectors therefore decide whether a short link fits DR4.

When does a link shorter than 500 m still need DR4+?

A link under 500 m still needs DR4+ when its connectors and splices push the channel loss above 3.0 dB. This happens on structured cabling where a link passes through several MPO patch panels or cassettes. To check, add up fiber length × attenuation, each mated connector pair and each splice, then compare the total with 3.0 dB (DR4) and 4.0 dB (DR4-2).

The table below uses worst-case planning allowances rather than measurements: 0.4 dB/km for OS2 cabled fiber (the IEEE assumption above), 0.75 dB per mated MPO connector pair and 0.3 dB per fusion splice (the ANSI/TIA-568.3 maximum allowances). Low-loss MPO components usually lose far less than 0.75 dB. Use your own measured loss results whenever you have them.

Example path (assumptions above) Fiber loss Connections and splices Total channel loss DR4 (≤500 m, ≤3.0 dB) DR4+ / DR4-2 (≤2 km, ≤4.0 dB)
150 m, 2 MPO pairs 0.06 dB 1.50 dB 1.56 dB Fits Fits (not needed)
450 m, 2 MPO pairs + 2 splices 0.18 dB 2.10 dB 2.28 dB Fits Fits (not needed)
400 m, 4 MPO pairs 0.16 dB 3.00 dB 3.16 dB Over budget at worst-case values: measure, or remove a patch point Fits
800 m, 4 MPO pairs 0.32 dB 3.00 dB 3.32 dB Out of range (length and loss) Fits
1.8 km, 4 MPO pairs + 2 splices 0.72 dB 3.60 dB 4.32 dB Out of range Over budget at worst-case values: needs measured loss ≤4.0 dB or fewer connections

The 400 m row shows the case that catches people out. The run is short, but four worst-case MPO connections use the whole DR4 budget. You have three options:

  • Measure the channel. If the measured worst lane is 3.0 dB or less, DR4 fits.
  • Remove a cross-connect so there are fewer mated pairs.
  • Specify DR4+ for that link.

The 1.8 km row shows that 2 km class optics have limits too. Long campus routes with many patch points need measured loss, not distance alone.

How should you test the fiber before choosing DR4 or DR4+?

Base the choice on the worst of the eight active fibers, not the average. A parallel optic fails as a link if any one lane fails.

  • Measure at 1310 nm. Use an MPO-capable light source and power meter or an optical loss test set (OLTS). Record insertion loss per fiber and keep the highest value.
  • Check fiber positions. On a 4-lane parallel MPO-12 interface, transmit uses positions 1–4 and receive uses positions 9–12; positions 5–8 are unused. Confirm that your trunk and patch cord polarity connects transmit to receive end to end.
  • Match APC to APC. Our DR4 and DR4+ modules use MPO-12/APC (angled) connectors. Do not mate an angled end face with a flat (UPC) one.
  • Inspect and clean every MPO end face before mating. Contamination adds loss and reflection, and this matters most on links close to their budget.
  • Read DOM after turn-up. Compare per-lane receive power with the module's alarm and warning thresholds to confirm margin. Our CMIS DOM acceptance guide explains how to read the fields.

Which 400G DR4 and DR4+ form factors are available?

Start with the host cage, then choose the reach. The table below lists the parallel single-mode 400G modules in our catalog, with figures taken from each product page.

Module Reach / fiber Host electrical interface Connector Max power (product page) Management
400G QSFP112 DR4 1310nm 500m 500 m, OS2 SMF 4 × 100G PAM4 MPO-12/APC ≤10.0 W CMIS 5.2
400G QSFP112 DR4+ 1310nm 2km 2 km, SMF 4 × 100G PAM4 MPO-12/APC ≤9 W CMIS 5.2
400G QSFP-DD DR4 1310nm 500m 500 m, OS2 SMF 4 × 100G PAM4 MPO-12/APC ≤10 W CMIS 4.0 / 5.0
400G OSFP-RHS DR4 1310nm 500m 500 m, OS2 SMF 4 × 100G PAM4 MPO-12/APC ≤10.0 W CMIS 5.2

Our catalog currently lists the 2 km parallel version in QSFP112 only. If a QSFP-DD switch needs 2 km and you don't need breakout, the 400G QSFP-DD FR4 1310nm 2km LC duplex module is another option. FR4 multiplexes four CWDM wavelengths onto one duplex LC fiber pair. It cannot break out into four 100G links, and both ends must be FR4. For an OSFP-RHS or QSFP-DD port that needs 2 km parallel optics, send us the port details and we will check what we can supply. For help choosing a form factor, see QSFP112 vs QSFP-DD vs OSFP-RHS.

Can you mix DR4 and DR4+ on the same link or in a 4×100G breakout?

Put the same specification at both ends of a 400G link: DR4 to DR4, or DR4+ to DR4+ of the same type. A mixed pair is only as good as its weaker end, so it gives you no 2 km reach. In a breakout, an MPO-to-4×LC harness splits the 400G module into four single-lane 100G single-mode links. Check each leg on its own. Under 500 m, the far-end optic is normally a 100G DR-type single-lane module. On longer legs, every optic at both ends must be rated for that distance and loss (for example, IEEE 100GBASE-FR1 is the 2 km single-lane specification). Before you order, ask us to confirm which 100G optics pair with the specific DR4 or DR4+ module.

What should you confirm about host compatibility?

Reach and loss decide DR4 versus DR4+. The host decides whether the module comes up. Compatibility depends on the host platform. Please share your switch model, software version, module type, link distance and fiber type so we can check coding and compatibility before you order. We offer coding for Cisco, Arista, NVIDIA Mellanox, Juniper and Dell hosts. YYGL Optical is an independent optics supplier; we are not those brands and we do not claim affiliation with them.

Pre-order checklist: DR4 or DR4+?

  • Longest link length in the batch (not the average), including patch cords.
  • Fiber type (OS2 or OS1a) and cable type (indoor or indoor/outdoor).
  • Number of mated MPO pairs and splices on the worst path.
  • Measured worst-lane insertion loss at 1310 nm, if available. Compare it with 3.0 dB (DR4) and 4.0 dB (DR4-2).
  • Connector type at both ends: MPO-12/APC, and whether patch cords are APC.
  • Polarity method, so transmit positions 1–4 reach receive positions 9–12.
  • Host cage (QSFP112, QSFP-DD or OSFP-RHS), switch or NIC model and software version.
  • Direct 400G link or 4×100G breakout, and the far-end optic type for each leg.
  • Whether you need the DR4+ datasheet to reference IEEE 400GBASE-DR4-2.

FAQ

Is DR4+ the same as 400GBASE-DR4-2?

Not always. 400GBASE-DR4-2 is the IEEE 802.3df name for 400G over eight single-mode fibers up to 2 km, with a 4.0 dB channel loss limit. "DR4+" is a market name, so check the datasheet to see which specification a given module follows.

Can I use a DR4+ module on a 100 m link?

The FOTC summary of 400GBASE-DR4-2 gives an operating range starting at 2 m, the same as DR4, so the standard expects short links to work. Check the minimum operating distance on the specific module's datasheet. Use DR4+ on short links when the patch path's loss is the problem.

Do I need new cabling to move from DR4 to DR4+?

Usually not. Both use four fiber pairs on an MPO connector at 1310 nm. What changes is the loss the optics can tolerate. Re-check polarity and APC end faces when you change the optics.

Does OS1a fiber change the answer?

Yes. Indoor OS1a cable can lose up to 1.0 dB/km, so the FOTC informative ranges shrink to 250 m for DR4 and 1 km for DR4-2. Use measured loss on OS1a plants.

Why not just order DR4+ for every link?

It is not required where DR4 fits. Order DR4 where your measured loss allows it, and keep DR4+ for links that are longer than 500 m or lose more than 3.0 dB. In our catalog, DR4+ is currently offered in QSFP112 only, while DR4 is available in QSFP112, QSFP-DD and OSFP-RHS.

Related reading

Have a link list ready? Request a quote with your lengths, measured losses and host models, and we will recommend DR4 or DR4+ for each link.

Written by the YYGL Optical Technical Team.