Technical diagram of reading DOM on 800G OSFP optics with CMIS 5.2 fields, 8-lane monitoring, and authentic YYGL 800G OSFP transceiver module

How to Read DOM on 800G OSFP Optics: CMIS 5.2 Fields to Check at Acceptance

On an 800G OSFP or QSFP-DD module, DOM is read through CMIS, not through the older SFF-8636 or SFF-8472 maps: module temperature and supply voltage sit in the lower memory page, Tx bias, Tx power and Rx power for each of the eight lanes sit on banked Page 11h, and the module's own alarm and warning thresholds sit on Page 02h. For incoming acceptance, record all of those values per module and per lane, compare them against the thresholds the module reports and the datasheet shipped with it, and also confirm the CMIS revision byte, the latched flags and which monitors the module advertises. A single "DOM supported" line on the host is not an acceptance result.

Module facts below come from the current YYGL Optical product pages, checked on 19 November 2026. Memory-map facts come from the OIF Common Management Interface Specification, Revision 5.2 (OIF-CMIS-05.2), and the CMIS decoder in the open-source Linux ethtool utility. We do not publish alarm thresholds, measured DOM values or test results here; those come from the module's own threshold page and your own bench.

Coding and supplier selection are covered in the 800G and 400G transceiver compatibility guide and Third-Party vs. OEM Optical Transceivers for AI Clusters: Compatibility, Testing, and TCO. This guide covers the next step: reading telemetry and deciding what to write down.

What does "CMIS 5.2 with DOM" on an 800G datasheet actually tell you?

It tells you which management map the host must speak and that diagnostics exist, not the alarm limits or which optional fields are present.

CMIS, published by the Optical Internetworking Forum (OIF), defines the management memory for multi-lane pluggables such as QSFP-DD, OSFP and QSFP112. Earlier modules used SFF-8472 (SFP/SFP+) and SFF-8636 (QSFP+/QSFP28). To show lane-level DOM on an 800G module, the host software must decode CMIS.

What each current YYGL Optical 800G and 1.6T product page states:

Module (product page) Form factor / optics Management (as listed) DOM telemetry named on the page Listed max power Case temperature
800G OSFP SR8, 850 nm, 100 m OSFP, 8×100G PAM4, Dual MPO-12/APC CMIS Rev 5.2 Laser bias, temperature, voltage, optical power (real-time via I2C) ≤16 W 0 °C to 70 °C
800G OSFP VR8, 850 nm, 50 m OSFP, 8×100G PAM4, Dual MPO-12/APC CMIS Rev 5.2 "Supported" (fields not itemized) ≤16 W 0 °C to 70 °C
800G OSFP DR8, 1310 nm, 500 m OSFP, 8×100G PAM4, Dual MPO-12/APC, SMF CMIS 5.2 (spec table) Operating temperature, supply voltage, laser bias current, Tx/Rx optical power ≤16 W 0 °C to 70 °C
800G OSFP DR8+, 1310 nm, 2 km OSFP, PAM4, Dual MPO-12/APC, SMF CMIS Rev 5.2 Temperature, voltage, optical power ≤16 W 0 °C to 70 °C
800G QSFP-DD SR8, 850 nm, 100 m QSFP-DD800, 8×100G PAM4, single MPO-16/APC CMIS Rev 5.2 Optical power, temperature, voltage (DDM/DOM via I2C) ≤15 W 0 °C to 70 °C
800G QSFP-DD VR8, 850 nm, 50 m QSFP-DD800, 8×100G PAM4, single MPO-16/APC CMIS Rev 5.2 Optical power, temperature, voltage ≤15 W 0 °C to 70 °C
1.6T OSFP224 DR4/DR8, 1310 nm, 500 m OSFP224, 8×200G PAM4, Dual MPO-12/APC, SMF CMIS Rev 5.2 Operating temperature, supply voltage, laser bias currents, Tx/Rx optical power ≤24.0 W 0 °C to 70 °C

The pages publish a management revision, a power ceiling and a case-temperature range, but not DOM alarm or warning thresholds. Acceptance limits must therefore come from the module's own Page 02h and the datasheet shipped with the lot. Also, "optical power" on a page that does not itemize Tx and Rx is not a confirmed per-lane Rx monitor; check what the module advertises.

Where do the DOM values live in CMIS memory?

CMIS splits monitoring into module-level and lane-level values, the main difference from single-channel SFP+ DDM.

CMIS location (OIF-CMIS-05.2) What it holds Scope Why it matters at acceptance
Lower page, byte 0 Identifier (for example QSFP-DD or OSFP, coded per SFF-8024) Module Confirms the host sees the form factor you ordered
Lower page, byte 1 CMIS revision (major.minor) Module Should match the revision on the datasheet; record it per lot
Lower page, byte 3 Module state (LowPwr, PwrUp, Ready, PwrDn, Fault) Module Read DOM only after the module reports Ready
Lower page, bytes 8–11 Module flags, including temperature and Vcc alarm/warning flags Module Latched; clear on read
Lower page, bytes 14–15 and 16–17 Module temperature (signed, 1/256 °C) and supply voltage (Vcc, 100 µV units) Module The two module-level monitors every CMIS module should report
Lower page 39–40; Page 00h vendor fields Active firmware; part number, serial, date code Module Ties every DOM record to one physical unit and firmware
Page 01h Advertising: which monitors and flags are implemented, Tx bias scaling, Rx power type (average or OMA) Module Tells you which DOM fields are real before you judge them
Page 02h Thresholds: high/low alarm and warning for temperature, Vcc, Tx power, Tx bias, Rx power One lane threshold set applies to all lanes Your pass/fail window, supplied by the module itself
Banked Page 11h, bytes 134–153 Lane flags: Tx fault, Tx/Rx LOS, Tx/Rx LOL, power and bias alarms/warnings Per lane Latched lane events since the last read
Banked Page 11h, bytes 154–201 Tx power, Tx bias and Rx power for lanes 1–8 (two bytes per lane) Per lane The eight-lane picture that a module-level "OK" hides
Pages 20h–2Fh (optional) Versatile Diagnostics Monitoring (VDM), such as pre-FEC error statistics or SNR, if advertised Varies Useful when present; do not assume it is implemented

Treat these offsets as a map for raw dumps, not a substitute for the specification.

How do you read DOM on an 800G module from the host?

Use the host's own decoder first and fall back to a raw page dump when a value looks wrong.

  • On a switch: most network operating systems offer a "show interfaces transceiver" style command; names and output vary by release. Check whether it prints all eight lanes or a summary.
  • On a Linux server or GPU host with a NIC port: ethtool -m <interface> decodes CMIS identity and diagnostics on recent ethtool versions. Options such as hex on, page and bank let you dump a specific page when you need to check a value against the raw bytes.
  • Wait for the right state. Read after ModuleReady with the data path active; power-up values are not acceptance data.
  • Rx needs light. Rx power is only meaningful with a known-good far-end module and a clean, verified patch. Record what the far end was.
  • "N/A" is not always a fault. Check Page 01h: the module may not advertise that monitor, or the host release may not decode it.

Which DOM values matter for incoming acceptance?

Five monitors, the flags and the identity fields. Judge each against Page 02h and the datasheet, then look for outliers across lanes and units.

Module temperature: is it inside the warning window under real airflow?

Every page above lists a 0 °C to 70 °C operating case temperature. The DOM value is the module's internal sensor, not automatically identical to a case measurement. Record it after the module settles under traffic in the real chassis, with port position and fan setting. A unit noticeably warmer than identical neighbours deserves a second look even without a warning flag.

Supply voltage: module or host?

The pages list a 3.3 V DC supply. Compare Vcc with Page 02h; if several modules in one switch read low together, suspect the host first.

Tx bias per lane: are all eight lanes consistent?

On 850 nm VCSEL-based SR8 and VR8 modules each lane has its own laser, so per-lane bias is a useful consistency check. Silicon-photonics DR8-class designs may report bias differently depending on laser arrangement; read Page 01h for bias support and scaling first. Never compare raw bias numbers across module types.

Tx power per lane: inside the window, and how wide is the spread?

Check every lane against the Page 02h Tx power warning thresholds, then record the spread between the highest and lowest lane. We do not suggest a pass limit; your baseline from the first good units of a lot becomes the reference.

Rx power per lane: is the far end and the fiber known?

Rx power tests the whole path: far-end transmitter, connectors, polarity and fiber. Use a short, inspected reference patch and a known-good far end so the reading reflects the unit under test. Note whether the module reports average power or OMA (Page 01h). On MPO-12/APC and MPO-16/APC parts, one dark lane often points to polarity, polish or a dirty end face; clean and inspect before rejecting anything.

Flags, revision and firmware: what does the module say about itself?

Flags are latched. Read once to clear insertion events, bring the link up, read again, and record anything still set. Record the CMIS revision byte, firmware, part number and serial. If the revision byte does not match the datasheet, ask the supplier before deploying the lot.

What should an 800G DOM acceptance record contain?

Use one record per module, with eight lane columns for the lane monitors. It fits a spreadsheet and can be attached to a purchase order or RMA case.

# Check Where to read it Module or per lane What to record Compare against
1 Identity Page 00h vendor fields Module Part number, serial, date code Packing list and purchase order
2 Form factor and CMIS revision Lower page bytes 0–1 Module Identifier, revision Datasheet (for example CMIS 5.2)
3 Firmware Lower page bytes 39–40 Module Active firmware version Lot record; same lot should match
4 Advertised monitors Page 01h Module Which monitors and flags are implemented; Rx power type Datasheet DOM list
5 Thresholds Page 02h Module (one lane set) All alarm/warning values as read Datasheet threshold table
6 Module state Lower page byte 3 Module Ready / Fault Must be Ready before readings 7–11
7 Temperature Lower page bytes 14–15 Module Value, port, fan setting, time under traffic Page 02h warnings; 0–70 °C case range on the page
8 Supply voltage Lower page bytes 16–17 Module Value Page 02h warnings; 3.3 V nominal
9 Tx bias Page 11h Per lane (1–8) Eight values or "not advertised" Page 02h; lane-to-lane consistency
10 Tx power Page 11h Per lane (1–8) Eight values and the max–min spread Page 02h; lot baseline
11 Rx power Page 11h Per lane (1–8) Eight values, far-end module serial, patch used Page 02h; lot baseline
12 Flags after link-up Lower page 8–11; Page 11h 134–153 Module and per lane Any flag set on the second read Should be clear; investigate any that remain

Keep the records: comparing later readings from the same port is how slow drift becomes visible before a link goes down.

How does this differ for 1.6T OSFP224 modules?

The method is the same; the scale changes. The 1.6T OSFP224 DR4/DR8 1310nm 500m module also lists CMIS Rev 5.2 and names temperature, supply voltage, laser bias currents and Tx/Rx optical power. Lanes carry 200G PAM4 and listed power rises to ≤24.0 W, so record temperature against 1.6T-class airflow. When run as two 800G ports, group lane records by port so each half traces to its own far end. Fiber-plant planning for that generation is covered in Planning a 1.6T OSFP224 DR8 Link, and host and cage questions in Compatible 1.6T OSFP224 for AI GPU Clusters.

Which 800G module types does this apply to?

All CMIS 800G types above, with small differences:

To choose between these optical types by reach and fiber, see 800G SR8 vs VR8 vs DR8 vs 2xFR4.

Pre-order checklist: what to settle before you order 800G optics

  • Host switch or NIC model, software or firmware version, and port type (OSFP or QSFP-DD800).
  • Whether that release decodes CMIS lane-level DOM.
  • Module type and reach (SR8, VR8, DR8, DR8+, or 1.6T OSFP224), measured link distance and fiber type.
  • Connector and polish on the patch plant: Dual MPO-12/APC, single MPO-16/APC, or duplex LC.
  • The datasheet threshold table and CMIS revision for the exact part.
  • Your acceptance template (above), reference patch and known-good far-end module.
  • Airflow and power budget planned to the listed maximum: ≤16 W (800G OSFP), ≤15 W (800G QSFP-DD), ≤24.0 W (1.6T OSFP224).

Compatibility depends on the host platform. Please share your switch model, software version, module type, link distance and fiber type so we can check coding and compatibility before you order. Coding is available for Cisco, Arista, NVIDIA Mellanox, Juniper and Dell hosts. YYGL Optical is an independent optics supplier; we are not those brands and we do not claim affiliation with them.

Ready to specify a lot? Send the items above through our request-a-quote form and ask for the datasheet threshold table for the exact module. More engineering guides are on the Tech Insights hub.

Frequently asked questions

Is DOM the same as DDM?

In everyday use, yes: both describe built-in monitoring of temperature, voltage, laser bias and optical power. What differs is the map: SFF-8472 for SFP/SFP+, SFF-8636 for QSFP+/QSFP28, and CMIS for 800G QSFP-DD and OSFP.

Where do I find alarm thresholds for an 800G module?

Read them from the module's CMIS Page 02h and compare them with the threshold table in the datasheet for that part. The YYGL Optical product pages list CMIS revision, power and case temperature, not DOM thresholds, so ask for the datasheet table when you order.

Why does my switch show only one Rx power value for an 800G module?

Some host releases summarize lanes or decode only part of the CMIS map, which carries eight Rx monitors on Page 11h. Check your software documentation, or dump Page 11h with ethtool, before concluding the module lacks per-lane monitors.

Can DOM prove that an 800G link is error-free?

No. Basic monitors show the module's operating point, not link error performance. Optional VDM statistics may help where advertised; host error counters remain the primary check.

Do I need to record DOM on every module, or only some?

Recording identity, firmware and the five monitors on every module costs little and gives each port a baseline. Full threshold dumps can be taken on a subset of each lot if revision and firmware match across the lot.