Side-view diagram comparing a standard OSFP module with its own finned heat sink in an OSFP cage against a 9.5 mm flat OSFP-RHS module cooled by a riding heat sink on the host cage, with the 6 mm forward-stop shift marked.

OSFP Finned Top vs Flat Top vs OSFP-RHS: Which Module Fits Your Switch or NIC Cage?

Short answer: a finned-top OSFP and a flat-top OSFP are both standard OSFP modules with their own integrated heat sink, and both are built for the standard OSFP cage you find on most 800G and 1.6T switch ports. OSFP-RHS is a different module: it is 9.5 mm high, has no heat sink of its own, and only fits an OSFP-RHS cage whose riding heat sink presses on it, which is the usual design on NICs and other low-profile hosts. So when a datasheet or a quote says “flat top”, confirm whether it means a closed-top integrated heat sink or OSFP-RHS before you order.

This guide uses the OSFP MSA specification (Rev 5.0, October 2022) to explain the three variants, how to tell which one a host expects, and what to put on a purchase order so the right module arrives. For the wider 400G form-factor picture (QSFP-DD vs QSFP112 vs OSFP-RHS), see our 400G form factor guide. This article covers one narrower question inside the OSFP family.

What do “finned top”, “flat top” and “RHS” actually mean?

The OSFP MSA defines one standard module with an integrated heat sink, and lets that heat sink take two shapes. It also defines a separate riding-heat-sink variant:

  • Open top (“finned top”) – section 3.4 of the MSA. The heat sink fins are exposed on top of the module. The spec only allows an open top when the fin pitch and dimensions meet its requirements, so the cage’s EMI fingers are not damaged and shielding still works. Air moving along the port passes straight through the fins.
  • Closed top (“flat top” with integrated heat sink) – section 3.3. The heat sink is still part of the module, but its top surface is closed and flat. The MSA defines a thermally conductive area on that surface with flatness and roughness limits, because in some hosts this area can also touch a riding heat sink mounted on a standard OSFP cage.
  • OSFP-RHS (Riding Heat Sink) – section 11. In the words of the MSA, a “9.5mm high pluggable module which does not have an integrated heat sink”. The heat sink belongs to the host: it sits on the OSFP-RHS cage and rides on the module’s flat top when the module is inserted.

Some vendors and switch makers also use “IHS” (integrated heat sink) for the first two and “RHS” for the third. That naming is clearer than “finned vs flat”, because a closed-top IHS module and an RHS module both look flat from above.

How do the three OSFP variants compare?

Attribute (per OSFP MSA Rev 5.0) OSFP, open top (finned) OSFP, closed top (flat, integrated heat sink) OSFP-RHS
Where the heat sink is On the module, fins exposed On the module, top closed On the host cage (riding heat sink)
Module height Standard OSFP height (heat sink included) Standard OSFP height (heat sink included) 9.5 mm, no heat sink (custom heights allowed, not defined in the spec)
Cage it is designed for Standard OSFP cage Standard OSFP cage (may also contact an optional riding heat sink) OSFP-RHS cage: lower port height, different positive stop and bezel cutout
Forward stop (datum B) Standard position Standard position Shifted 6 mm, so the module cannot be fully inserted into a standard OSFP cage
Module airflow requirement (section 10.2) Applies Applies Not applicable
Max riding-heat-sink down force on the module 36 N, only if the cage has the optional riding heat sink 36 N, only if the cage has the optional riding heat sink 50 N
Thermal contact surface flatness — 0.12 mm or better (0.075 mm recommended above 20 W) 0.15 mm (≤5 W), 0.12 mm (>5 W), 0.05 mm recommended above 14 W
Connector, host PCB footprint, electrical and management interface Identical across all three (the RHS table in section 11 states connector, PCB layout, electrical interface and management are identical to OSFP)
Typical hosts Switch front panels with front-to-back airflow Switch ports whose thermal design calls for a closed top Server NICs, PCIe adapters and other low-profile or riding-heat-sink hosts; some switch SKUs

Two points from the table matter most in practice. First, the electrical side is the same, so the difference is purely mechanical and thermal: the host will not “see” a different module, it will just not accept or cool the wrong one. Second, the MSA deliberately moved the RHS forward stop so the module cannot be fully seated in a standard cage. If an RHS module stops short in a port, that is the design working, not a fault.

Can an OSFP-RHS module go into a standard OSFP switch port?

No. Section 11.2 of the MSA shifts the forward-stop datum by 6 mm “to prevent an OSFP-RHS from being fully inserted into an OSFP cage”. Even if it could be pushed in, a standard OSFP cage has no heat sink riding on top of it, so a module with no heat sink of its own would have no cooling path.

The reverse also fails. An integrated-heat-sink OSFP is taller than the 9.5 mm RHS body, and the RHS cage has a lower port height and its own bezel cutout, so a finned or closed-top OSFP will not enter an RHS port.

Are finned-top and flat-top (closed-top) OSFP interchangeable?

Mechanically, both are standard OSFP modules built for the standard cage, so both will usually seat. Whether a host accepts either one is a thermal and qualification question, not a mechanical one:

  • Fins expose more surface to the airflow along the port. A closed top relies on the air flowing over and around it, or on a riding heat sink if the cage has one.
  • A host’s thermal design is worked out for a given module power and airflow. If the platform documentation names one heat-sink style for a port or a power level, follow it.
  • High-power modules make this stricter. Our 1.6T OSFP224 DR8 (≤24 W listed) sits in a very different thermal class from a 800G OSFP SR8 at ≤16 W, so do not assume the heat-sink style that suited one port speed suits the next.

For context on why power per port keeps climbing, and where LPO and silicon photonics change the thermal budget, see DSP vs LPO vs silicon photonics in high-density racks.

Why do switches and NICs usually use different OSFP variants?

A switch front panel has room above each port and strong front-to-back airflow, so a module that carries its own fins works well. A PCIe adapter has to stay inside a low card profile, and its airflow comes from the server chassis rather than from dedicated port fans. Moving the heat sink onto the cage (RHS) lets the card designer choose its size and shape, and keeps the module itself at 9.5 mm.

That is why a common AI and HPC pattern is: standard OSFP on the switch, OSFP-RHS (or QSFP112) on the server NIC, joined by the same optical standard. A 800G OSFP DR8 on the switch can feed two 400G OSFP-RHS DR4 modules on the NICs over an MPO split, if the switch software supports that breakout. On multimode, the NIC-side equivalent is the 400G OSFP-RHS SR4 (100 m on OM4). The heat-sink style differs at each end, while the optics on each fiber lane match. For DR4 reach limits see 400G DR4 vs DR4+; for multimode reach, 400G SR4 vs VR4 on OM3/OM4/OM5.

RHS is not limited to NICs. Some switch platforms are offered in both integrated-heat-sink and riding-heat-sink port versions, so the same switch family can need different modules depending on the exact SKU. Always read the variant from the specific model number’s documentation.

How do you tell which variant a host needs?

  1. Read the host’s optics or hardware guide for the exact model. Look for “OSFP-RHS”, “riding heat sink”, “IHS”, “integrated heat sink”, “open top” or “closed top”. Treat a bare “flat top” as unresolved until you know which of these it means.
  2. Look at the cage. An RHS port has a heat sink mounted on the cage itself, sitting over the module opening. A standard OSFP port is an open cage, with the module bringing its own heat sink.
  3. Measure an existing module. A 9.5 mm body with no fins or heat-sink block is RHS. A taller body with a fin stack or a closed heat-sink block is standard OSFP.
  4. Do not rely on the pull-tab colour. The MSA colour code (beige for 850 nm, yellow for 1310 nm up to 500 m, green for 2 km, and so on) identifies the optical type, not the heat-sink style.
  5. Check the module power the port supports. The MSA allows up to 10 A on four 3.3 V power pins and defines eight power classes; the host decides which class a port can cool.

Which YYGL OSFP modules come in which variant?

Module Variant listed on the product page Optical interface Typical host side
800G OSFP SR8, 850 nm, 100 m OSFP, finned top or flat top Dual MPO-12/APC, multimode Switch
800G OSFP DR8, 1310 nm, 500 m OSFP, finned or flat top Dual MPO-12/APC, single-mode Switch
1.6T OSFP224 DR8, 1310 nm, 500 m OSFP224, finned top or flat top Dual MPO-12/APC, single-mode Switch
400G OSFP-RHS DR4, 1310 nm, 500 m OSFP-RHS MPO-12/APC, single-mode NIC / adapter
400G OSFP-RHS SR4, 850 nm, 100 m OSFP-RHS MPO-12/APC, multimode NIC / adapter

Where a product page lists “flat top available”, tell us whether your host needs a closed-top integrated heat sink or OSFP-RHS, and we will confirm which build we can supply for that host before you order.

Pre-order checklist: OSFP heat-sink variant

  • Exact host model and SKU (switch or NIC), and the port type its documentation names: OSFP (IHS, open or closed top) or OSFP-RHS.
  • Whether the host documentation restricts the heat-sink style per port or per power level.
  • Module power class the port supports, compared with the module’s listed maximum power.
  • Chassis airflow direction and any blank or adjacent-port rules in the host guide.
  • Optical type and reach at both ends of the link (for example DR8 on the switch and DR4 on the NIC), plus fiber type, MPO-12 APC polarity and breakout mode support.
  • Host software or firmware version, so coding can be checked. See how to read DOM on 800G OSFP optics for what to check at acceptance.

We supply OSFP and OSFP-RHS modules for hosts such as Cisco, Arista, NVIDIA Mellanox, Juniper and Dell. Compatibility depends on the host platform. Please share your switch model, software version, module type, link distance and fiber type so we can check coding and compatibility before you order.

YYGL Optical is an independent optics supplier; we are not those brands and we do not claim affiliation with them.

Request a quote for OSFP or OSFP-RHS modules and include the host model and port variant from the checklist above.

FAQ

Is OSFP-RHS the same as a flat-top OSFP?

Not necessarily. “Flat top” can describe a standard OSFP with a closed-top integrated heat sink, or an OSFP-RHS with no heat sink at all. They fit different cages. Ask which one is meant.

Will an OSFP-RHS module work in a switch with standard OSFP ports?

No. The MSA shifts the RHS forward stop by 6 mm so it cannot be fully inserted into a standard OSFP cage, and a standard cage has no riding heat sink to cool it.

Do OSFP and OSFP-RHS modules link to each other over fiber?

Yes, if both ends use the same optical specification. The heat-sink style affects only the host port. A 400G DR4 link, for example, depends on both ends being DR4, not on both being the same mechanical variant.

Is a finned-top OSFP always better for cooling than a closed top?

Not in every host. The right choice is the one the host’s thermal design was worked out for. Follow the platform documentation for the port and module power level.

Is the electrical interface different on OSFP-RHS?

No. The MSA states that the connector, host PCB footprint, electrical interface and management interface are identical to OSFP. Only the module height, positive stop, cage and cooling differ.

Source: OSFP MSA, “Specification for OSFP Octal Small Form Factor Pluggable Module”, Rev 5.0 (October 2, 2022), sections 3.3, 3.4, 3.8, 5.5, 11 and 13.6, osfpmsa.org. Product variants and power figures are as listed on the YYGL product pages linked above.